Short answer: A valve moved by an air-pressure diaphragm or piston actuator against a spring; air-to-open valves open with air (fail closed), air-to-close valves close with air (fail open).
Why
Instrument air is safe in hazardous areas and the spring gives a defined fail position.
How
- DCS sends 4–20 mA → I/P converter or smart positioner → 0.2–1.0 bar (3–15 psi) air to the actuator.
- Positioner compares actual stem position with the signal and corrects it.
- Choose fail position by safety: fuel valve FC, cooling water FO.
Likely focus at
IOCL, HPCL, BPCL, NRL, MRPL, CPCL, ONGC, Oil India, GAIL, BCPL, EIL, NFL, RCF, BVFCL, NPCIL, Heavy Water Board. Organisation names show where a topic is a likely focus because of what the organisation does; they are not claims that a particular question was asked. Recruitment routes change each year, so confirm in the official notification.
Frequently asked questions
What is a pneumatic control valve? What do air-to-open and air-to-close mean?
A valve moved by an air-pressure diaphragm or piston actuator against a spring; air-to-open valves open with air (fail closed), air-to-close valves close with air (fail open). Why: Instrument air is safe in hazardous areas and the spring gives a defined fail position.