Short answer: The relation between valve opening and flow at constant ΔP: linear (flow ∝ opening), equal percentage (each step adds a fixed % of existing flow), quick opening.
Why
Installed behaviour depends on how much of the system pressure drop the valve takes; equal-percentage valves become nearly linear when the valve takes a small share of ΔP.
How
- Equal percentage: most process loops (pressure, temperature, flow with varying ΔP).
- Linear: level control and where valve ΔP is constant.
- Quick opening: on/off and relief duty.
- Size so normal flow is at 50–70 % opening.
Likely focus at
IOCL, HPCL, BPCL, NRL, MRPL, CPCL, ONGC, Oil India, GAIL, BCPL, EIL. Organisation names show where a topic is a likely focus because of what the organisation does; they are not claims that a particular question was asked. Recruitment routes change each year, so confirm in the official notification.
Frequently asked questions
What is a control valve characteristic? Linear vs equal percentage.
The relation between valve opening and flow at constant ΔP: linear (flow ∝ opening), equal percentage (each step adds a fixed % of existing flow), quick opening. Why: Installed behaviour depends on how much of the system pressure drop the valve takes; equal-percentage valves become nearly linear when the valve takes a small share of ΔP.