JLEE IE · 11 practice questions with answers

Practise and take a mock test →

Controllers, final control elements and automation

Topics: Process variables and dynamics, dead time; on–off, P, PI, PD and PID control; tuning (Ziegler–Nichols); feedback, feed-forward, cascade and ratio control; control valves, characteristics, actuators, positioners, I/P converters; PLC architecture and ladder logic; DCS and SCADA; P&ID symbols.

Process dynamics and controller modes

Processes have capacity (giving first-order lags) and often dead time. On–off control is simple but cycles. Proportional control leaves an offset (for a unit set-point change with process gain K, offset = 1/(1 + K_cK)); integral action removes the offset but adds overshoot; derivative action anticipates and damps. Proportional band PB = 100/K_c %.

  • P: offset; I: removes offset; D: damps
  • PB = 100/K_c %
  • Offset = 1/(1 + K_c K)

Example: A controller has a proportional band of 25 %. Find K_c.

  1. K_c = 100/25.
  2. = 4.

Answer: 4

Example: With K_c = 4 and process gain 1, find the offset after a unit set-point change (P only).

  1. Offset = 1/(1 + 4 × 1).
  2. = 0.2 (20 %).

Answer: 0.2

Tuning and control strategies

Ziegler–Nichols (ultimate gain method): raise P gain until steady oscillation at K_u with period P_u; then PID: K_c = 0.6K_u, T_i = P_u/2, T_d = P_u/8. Strategies: feedback, feed-forward (acts on measured disturbances), cascade (a fast inner loop under a slow outer loop), ratio control (keeps two flows in proportion), split range and override.

  • Z–N PID: 0.6K_u, P_u/2, P_u/8
  • Cascade: inner loop faster
  • Ratio: B = r × A

Example: K_u = 8 and P_u = 10 s. Find the Ziegler–Nichols PID settings.

  1. K_c = 0.6 × 8 = 4.8.
  2. T_i = 10/2 = 5 s; T_d = 10/8 = 1.25 s.

Answer: K_c 4.8, T_i 5 s, T_d 1.25 s

Example: A ratio controller keeps B = 2 × A. Flow A is 50 L/min. What is B’s set point?

  1. B = 2 × 50.
  2. = 100 L/min.

Answer: 100 L/min

Final control elements and PLCs

Control valves have characteristics: linear, equal percentage (most common for process control) and quick opening (on–off). Air-to-open valves fail closed; air-to-close valves fail open: choose for safety. I/P converters turn 4–20 mA into 3–15 psi (0.2–1.0 bar) air; positioners ensure the stem goes where it is told. PLCs run ladder logic in a scan cycle (read inputs, run program, write outputs).

  • Air-to-open = fail closed
  • 4–20 mA → 3–15 psi
  • PLC scan: inputs, logic, outputs

Example: An I/P converter receives 12 mA. Find its output pressure (3–15 psi).

  1. 12 mA is half of the 4–20 mA span.
  2. 3 + 0.5 × 12 = 9 psi.

Answer: 9 psi

Example: A steam valve to a reactor must shut if air fails. Air-to-open or air-to-close?

  1. It must close when the air signal is lost.
  2. Air-to-open (fail closed).

Answer: Air-to-open

Proportional control leaves offset, integral removes it, and derivative anticipates rate of change. Proportional band = 100/K_c. On–off control is simple, but cycles about the set point. Cascade control uses a fast secondary loop inside a primary one; ratio control keeps two flows proportional; feed-forward acts on a measured disturbance. Control valves have quick-opening, linear or equal-percentage characteristics, and fail-safe action is air-to-open or air-to-close. An I/P converter turns 4–20 mA into 3–15 psi. A PLC scans inputs, runs a ladder program and writes outputs in a repeating cycle. SCADA supervises plants through RTUs and HMIs, and a DCS distributes control across controllers.

  • Ziegler–Nichols: P: K_c = 0.5K_u; PI: 0.45K_u, τᵢ = P_u/1.2; PID: 0.6K_u, τᵢ = P_u/2, τ_d = P_u/8.
  • Valve C_v: Q = C_v√(ΔP/SG).
  • Ladder: NO and NC contacts, coils, timers, counters.
  • P&ID tag FIC = flow indicating controller.
  • Air-to-open valves fail closed.

Key formulas

  • PB = 100/K_c
  • u = K_c(e + (1/τᵢ)∫e dt + τ_d de/dt)
  • Q = C_v√(ΔP/SG)

Practice questions

Offset is removed by

  1. proportional
  2. integral
  3. derivative
  4. on–off
Show the answer

Answer: B. integral Reset.

Derivative action responds to

  1. error magnitude
  2. rate of change of error
  3. time integral
  4. set point only
Show the answer

Answer: B. rate of change of error Anticipates.

Proportional band with K_c = 2 is

  1. 2%
  2. 20%
  3. 50%
  4. 200%
Show the answer

Answer: C. 50% 100/2.

A PLC’s scan begins with

  1. reading inputs
  2. printing
  3. tuning loops
  4. writing to SCADA only
Show the answer

Answer: A. reading inputs Input, program, output.

An air-to-open valve on air failure

  1. fails closed
  2. fails open
  3. stays half
  4. pumps
Show the answer

Answer: A. fails closed Spring closes.

An I/P converter gives

  1. pneumatic from current
  2. current from voltage
  3. digital from analogue
  4. power from air
Show the answer

Answer: A. pneumatic from current To the valve.

A loop inside another loop is

  1. cascade
  2. ratio
  3. on–off
  4. open-loop
Show the answer

Answer: A. cascade Secondary fast loop.

Feed-forward acts on

  1. a measured disturbance
  2. the offset
  3. the set point error
  4. noise only
Show the answer

Answer: A. a measured disturbance Before error appears.

In P&ID tags, TIC stands for

  1. temperature indicating controller
  2. total input current
  3. timer in control
  4. tank inlet check
Show the answer

Answer: A. temperature indicating controller ISA codes.

The relay logic-like PLC language is

  1. ladder diagram
  2. Java
  3. HTML
  4. SQL
Show the answer

Answer: A. ladder diagram IEC 61131.

For ratio control you keep

  1. two flows in proportion
  2. pressure zero
  3. time constant
  4. valve closed
Show the answer

Answer: A. two flows in proportion Blending.

The practice questions were written for this studio; they are not copied from ASTU papers. ASTU publishes no topic syllabus for these exams, so the topics are an informed guide based on diploma courses, not an official list.