Controllers, final control elements and automation
Topics: Process variables and dynamics, dead time; on–off, P, PI, PD and PID control; tuning (Ziegler–Nichols); feedback, feed-forward, cascade and ratio control; control valves, characteristics, actuators, positioners, I/P converters; PLC architecture and ladder logic; DCS and SCADA; P&ID symbols.
Process dynamics and controller modes
Processes have capacity (giving first-order lags) and often dead time. On–off control is simple but cycles. Proportional control leaves an offset (for a unit set-point change with process gain K, offset = 1/(1 + K_cK)); integral action removes the offset but adds overshoot; derivative action anticipates and damps. Proportional band PB = 100/K_c %.
- P: offset; I: removes offset; D: damps
- PB = 100/K_c %
- Offset = 1/(1 + K_c K)
Example: A controller has a proportional band of 25 %. Find K_c.
- K_c = 100/25.
- = 4.
Answer: 4
Example: With K_c = 4 and process gain 1, find the offset after a unit set-point change (P only).
- Offset = 1/(1 + 4 × 1).
- = 0.2 (20 %).
Answer: 0.2
Tuning and control strategies
Ziegler–Nichols (ultimate gain method): raise P gain until steady oscillation at K_u with period P_u; then PID: K_c = 0.6K_u, T_i = P_u/2, T_d = P_u/8. Strategies: feedback, feed-forward (acts on measured disturbances), cascade (a fast inner loop under a slow outer loop), ratio control (keeps two flows in proportion), split range and override.
- Z–N PID: 0.6K_u, P_u/2, P_u/8
- Cascade: inner loop faster
- Ratio: B = r × A
Example: K_u = 8 and P_u = 10 s. Find the Ziegler–Nichols PID settings.
- K_c = 0.6 × 8 = 4.8.
- T_i = 10/2 = 5 s; T_d = 10/8 = 1.25 s.
Answer: K_c 4.8, T_i 5 s, T_d 1.25 s
Example: A ratio controller keeps B = 2 × A. Flow A is 50 L/min. What is B’s set point?
- B = 2 × 50.
- = 100 L/min.
Answer: 100 L/min
Final control elements and PLCs
Control valves have characteristics: linear, equal percentage (most common for process control) and quick opening (on–off). Air-to-open valves fail closed; air-to-close valves fail open: choose for safety. I/P converters turn 4–20 mA into 3–15 psi (0.2–1.0 bar) air; positioners ensure the stem goes where it is told. PLCs run ladder logic in a scan cycle (read inputs, run program, write outputs).
- Air-to-open = fail closed
- 4–20 mA → 3–15 psi
- PLC scan: inputs, logic, outputs
Example: An I/P converter receives 12 mA. Find its output pressure (3–15 psi).
- 12 mA is half of the 4–20 mA span.
- 3 + 0.5 × 12 = 9 psi.
Answer: 9 psi
Example: A steam valve to a reactor must shut if air fails. Air-to-open or air-to-close?
- It must close when the air signal is lost.
- Air-to-open (fail closed).
Answer: Air-to-open
Proportional control leaves offset, integral removes it, and derivative anticipates rate of change. Proportional band = 100/K_c. On–off control is simple, but cycles about the set point. Cascade control uses a fast secondary loop inside a primary one; ratio control keeps two flows proportional; feed-forward acts on a measured disturbance. Control valves have quick-opening, linear or equal-percentage characteristics, and fail-safe action is air-to-open or air-to-close. An I/P converter turns 4–20 mA into 3–15 psi. A PLC scans inputs, runs a ladder program and writes outputs in a repeating cycle. SCADA supervises plants through RTUs and HMIs, and a DCS distributes control across controllers.
- Ziegler–Nichols: P: K_c = 0.5K_u; PI: 0.45K_u, τᵢ = P_u/1.2; PID: 0.6K_u, τᵢ = P_u/2, τ_d = P_u/8.
- Valve C_v: Q = C_v√(ΔP/SG).
- Ladder: NO and NC contacts, coils, timers, counters.
- P&ID tag FIC = flow indicating controller.
- Air-to-open valves fail closed.
Key formulas
- PB = 100/K_c
- u = K_c(e + (1/τᵢ)∫e dt + τ_d de/dt)
- Q = C_v√(ΔP/SG)
Practice questions
Offset is removed by
- proportional
- integral
- derivative
- on–off
Show the answer
Answer: B. integral Reset.
Derivative action responds to
- error magnitude
- rate of change of error
- time integral
- set point only
Show the answer
Answer: B. rate of change of error Anticipates.
Proportional band with K_c = 2 is
- 2%
- 20%
- 50%
- 200%
Show the answer
Answer: C. 50% 100/2.
A PLC’s scan begins with
- reading inputs
- printing
- tuning loops
- writing to SCADA only
Show the answer
Answer: A. reading inputs Input, program, output.
An air-to-open valve on air failure
- fails closed
- fails open
- stays half
- pumps
Show the answer
Answer: A. fails closed Spring closes.
An I/P converter gives
- pneumatic from current
- current from voltage
- digital from analogue
- power from air
Show the answer
Answer: A. pneumatic from current To the valve.
A loop inside another loop is
- cascade
- ratio
- on–off
- open-loop
Show the answer
Answer: A. cascade Secondary fast loop.
Feed-forward acts on
- a measured disturbance
- the offset
- the set point error
- noise only
Show the answer
Answer: A. a measured disturbance Before error appears.
In P&ID tags, TIC stands for
- temperature indicating controller
- total input current
- timer in control
- tank inlet check
Show the answer
Answer: A. temperature indicating controller ISA codes.
The relay logic-like PLC language is
- ladder diagram
- Java
- HTML
- SQL
Show the answer
Answer: A. ladder diagram IEC 61131.
For ratio control you keep
- two flows in proportion
- pressure zero
- time constant
- valve closed
Show the answer
Answer: A. two flows in proportion Blending.