Measuring process variables

Topics: Pressure: manometers, Bourdon tube, bellows, diaphragm, McLeod and Pirani gauges; flow: orifice, venturi, rotameter, magnetic, turbine, ultrasonic, Coriolis; level: float, displacer, differential pressure, capacitance, ultrasonic; temperature: bimetal, RTD, thermistor, thermocouple, pyrometers; viscosity, humidity, density.

Pressure measurement

Units: 1 bar = 100 kPa ≈ 750 mmHg ≈ 10.2 m of water. Manometers and U-tubes for low pressures; Bourdon tubes, bellows and diaphragms for gauges; strain-gauge and capacitive transmitters for process work. Vacuum: McLeod gauge (reference), Pirani (thermal conductivity) and ionisation gauges for very low pressures. Absolute = gauge + atmospheric.

  • 1 bar ≈ 750 mmHg ≈ 10.2 m H₂O
  • Bourdon: gauge pressure
  • Pirani, McLeod: vacuum

Example: Express 1 bar in metres of water.

  1. h = p/ρg = 100 000/(1000 × 9.81).
  2. ≈ 10.2 m.

Answer: ≈ 10.2 m

Example: Which gauge measures vacuum by the cooling of a heated wire?

  1. Heat loss depends on gas pressure at low pressures.
  2. The Pirani gauge.

Answer: Pirani

Flow measurement

Head meters (orifice, venturi, flow nozzle, pitot) give Q ∝ √Δp. Variable-area rotameters read directly; magnetic flowmeters use Faraday’s law e = BDv (conductive liquids only); turbine meters give pulses proportional to volume; ultrasonic and vortex meters have no moving parts; Coriolis meters measure mass flow directly.

  • Q ∝ √Δp
  • Magnetic: e = B D v
  • Coriolis: mass flow

Example: A magnetic flowmeter has B = 0.1 T, pipe diameter 0.1 m and velocity 2 m/s. Find the EMF.

  1. e = BDv = 0.1 × 0.1 × 2.
  2. = 0.02 V = 20 mV.

Answer: 20 mV

Example: A turbine meter gives 100 pulses per litre. At 500 pulses per second, what is the flow?

  1. 500/100 = 5 L/s.
  2. = 300 L/min.

Answer: 5 L/s

Level and temperature measurement

Level: sight glass, float, displacer, DP (h = Δp/ρg), capacitance, ultrasonic and radar (distance from echo time, level = tank height − distance). Temperature: thermistors (narrow, sensitive), RTDs (about −200 to 850 °C, accurate), thermocouples (up to about 1800 °C), radiation pyrometers (non-contact, very hot bodies).

  • DP level: h = Δp/ρg
  • Ultrasonic: distance = v t/2
  • Pyrometer: no contact, high T

Example: A DP transmitter on a water tank reads 29.43 kPa. Find the level.

  1. h = 29 430/(1000 × 9.81).
  2. = 3 m.

Answer: 3 m

Example: An ultrasonic gauge on top of a 5 m tank hears its echo after 10 ms (sound 343 m/s). Find the level.

  1. Distance = 343 × 0.01/2 ≈ 1.715 m.
  2. Level = 5 − 1.715 ≈ 3.29 m.

Answer: ≈ 3.29 m

Elastic elements measure gauge pressure: Bourdon tubes (high), bellows (low to medium), diaphragms (low). McLeod and Pirani gauges read vacuum. Head flowmeters have Q ∝ √ΔP; a rotameter is variable-area; magnetic meters need conductive fluid, following Faraday’s law; Coriolis meters measure mass flow directly. Level uses p = ρgh in differential-pressure transmitters. RTDs (Pt100, 100 Ω at 0 °C, α ≈ 0.00385) are accurate and near linear; thermocouples follow the Seebeck effect, needing cold-junction compensation. Radiation pyrometers measure very high temperature without contact.

  • Thermocouples: K (chromel–alumel), J (iron–constantan), S/R (Pt–Rh).
  • Orifice has highest permanent loss; venturi the lowest of head meters.
  • Hygrometers measure humidity; psychrometers use wet and dry bulbs.
  • Redwood and Saybolt viscometers read efflux time.
  • Zero suppression and elevation adjust DP level transmitters.

Key formulas

  • Q ∝ √ΔP
  • R = R₀(1 + αΔT)
  • p = ρgh
  • Q = C_d A√(2gh)

Practice questions

An orifice flowmeter’s flow is proportional to

  1. ΔP
  2. √ΔP
  3. ΔP²
  4. 1/ΔP
Show the answer

Answer: B. √ΔP Head meter.

A magnetic flowmeter requires fluid that is

  1. conductive
  2. non-conductive
  3. gaseous
  4. cold only
Show the answer

Answer: A. conductive Faraday’s law.

Mass flow is measured directly by a

  1. Coriolis meter
  2. pitot tube
  3. rotameter
  4. weir
Show the answer

Answer: A. Coriolis meter Tube twist.

A Pt100 at 0 °C has resistance

  1. 0 Ω
  2. 10 Ω
  3. 100 Ω
  4. 1000 Ω
Show the answer

Answer: C. 100 Ω Name.

A thermocouple works on the

  1. Seebeck effect
  2. Hall effect
  3. Doppler effect
  4. Coriolis effect
Show the answer

Answer: A. Seebeck effect Thermo-EMF.

Type K thermocouple is

  1. chromel–alumel
  2. iron–constantan
  3. copper–constantan
  4. Pt–Rh
Show the answer

Answer: A. chromel–alumel General purpose.

Very high vacuum is measured by

  1. Bourdon tube
  2. McLeod gauge
  3. bellows
  4. U-tube only
Show the answer

Answer: B. McLeod gauge Compressed gas.

A rotameter is a

  1. variable-area meter
  2. head meter
  3. turbine meter
  4. magnetic meter
Show the answer

Answer: A. variable-area meter Float in taper tube.

Hot metal in furnaces is measured by a

  1. radiation pyrometer
  2. mercury thermometer
  3. RTD
  4. bimetal strip
Show the answer

Answer: A. radiation pyrometer Non-contact.

Liquid level by DP depends on

  1. ρgh
  2. flow speed
  3. colour
  4. viscosity only
Show the answer

Answer: A. ρgh Hydrostatic.

Bourdon tubes measure

  1. pressure
  2. temperature only
  3. flow only
  4. pH
Show the answer

Answer: A. pressure Elastic deformation.