Measuring process variables
Topics: Pressure: manometers, Bourdon tube, bellows, diaphragm, McLeod and Pirani gauges; flow: orifice, venturi, rotameter, magnetic, turbine, ultrasonic, Coriolis; level: float, displacer, differential pressure, capacitance, ultrasonic; temperature: bimetal, RTD, thermistor, thermocouple, pyrometers; viscosity, humidity, density.
Pressure measurement
Units: 1 bar = 100 kPa ≈ 750 mmHg ≈ 10.2 m of water. Manometers and U-tubes for low pressures; Bourdon tubes, bellows and diaphragms for gauges; strain-gauge and capacitive transmitters for process work. Vacuum: McLeod gauge (reference), Pirani (thermal conductivity) and ionisation gauges for very low pressures. Absolute = gauge + atmospheric.
- 1 bar ≈ 750 mmHg ≈ 10.2 m H₂O
- Bourdon: gauge pressure
- Pirani, McLeod: vacuum
Example: Express 1 bar in metres of water.
- h = p/ρg = 100 000/(1000 × 9.81).
- ≈ 10.2 m.
Answer: ≈ 10.2 m
Example: Which gauge measures vacuum by the cooling of a heated wire?
- Heat loss depends on gas pressure at low pressures.
- The Pirani gauge.
Answer: Pirani
Flow measurement
Head meters (orifice, venturi, flow nozzle, pitot) give Q ∝ √Δp. Variable-area rotameters read directly; magnetic flowmeters use Faraday’s law e = BDv (conductive liquids only); turbine meters give pulses proportional to volume; ultrasonic and vortex meters have no moving parts; Coriolis meters measure mass flow directly.
- Q ∝ √Δp
- Magnetic: e = B D v
- Coriolis: mass flow
Example: A magnetic flowmeter has B = 0.1 T, pipe diameter 0.1 m and velocity 2 m/s. Find the EMF.
- e = BDv = 0.1 × 0.1 × 2.
- = 0.02 V = 20 mV.
Answer: 20 mV
Example: A turbine meter gives 100 pulses per litre. At 500 pulses per second, what is the flow?
- 500/100 = 5 L/s.
- = 300 L/min.
Answer: 5 L/s
Level and temperature measurement
Level: sight glass, float, displacer, DP (h = Δp/ρg), capacitance, ultrasonic and radar (distance from echo time, level = tank height − distance). Temperature: thermistors (narrow, sensitive), RTDs (about −200 to 850 °C, accurate), thermocouples (up to about 1800 °C), radiation pyrometers (non-contact, very hot bodies).
- DP level: h = Δp/ρg
- Ultrasonic: distance = v t/2
- Pyrometer: no contact, high T
Example: A DP transmitter on a water tank reads 29.43 kPa. Find the level.
- h = 29 430/(1000 × 9.81).
- = 3 m.
Answer: 3 m
Example: An ultrasonic gauge on top of a 5 m tank hears its echo after 10 ms (sound 343 m/s). Find the level.
- Distance = 343 × 0.01/2 ≈ 1.715 m.
- Level = 5 − 1.715 ≈ 3.29 m.
Answer: ≈ 3.29 m
Elastic elements measure gauge pressure: Bourdon tubes (high), bellows (low to medium), diaphragms (low). McLeod and Pirani gauges read vacuum. Head flowmeters have Q ∝ √ΔP; a rotameter is variable-area; magnetic meters need conductive fluid, following Faraday’s law; Coriolis meters measure mass flow directly. Level uses p = ρgh in differential-pressure transmitters. RTDs (Pt100, 100 Ω at 0 °C, α ≈ 0.00385) are accurate and near linear; thermocouples follow the Seebeck effect, needing cold-junction compensation. Radiation pyrometers measure very high temperature without contact.
- Thermocouples: K (chromel–alumel), J (iron–constantan), S/R (Pt–Rh).
- Orifice has highest permanent loss; venturi the lowest of head meters.
- Hygrometers measure humidity; psychrometers use wet and dry bulbs.
- Redwood and Saybolt viscometers read efflux time.
- Zero suppression and elevation adjust DP level transmitters.
Key formulas
- Q ∝ √ΔP
- R = R₀(1 + αΔT)
- p = ρgh
- Q = C_d A√(2gh)
Practice questions
An orifice flowmeter’s flow is proportional to
- ΔP
- √ΔP
- ΔP²
- 1/ΔP
Show the answer
Answer: B. √ΔP Head meter.
A magnetic flowmeter requires fluid that is
- conductive
- non-conductive
- gaseous
- cold only
Show the answer
Answer: A. conductive Faraday’s law.
Mass flow is measured directly by a
- Coriolis meter
- pitot tube
- rotameter
- weir
Show the answer
Answer: A. Coriolis meter Tube twist.
A Pt100 at 0 °C has resistance
- 0 Ω
- 10 Ω
- 100 Ω
- 1000 Ω
Show the answer
Answer: C. 100 Ω Name.
A thermocouple works on the
- Seebeck effect
- Hall effect
- Doppler effect
- Coriolis effect
Show the answer
Answer: A. Seebeck effect Thermo-EMF.
Type K thermocouple is
- chromel–alumel
- iron–constantan
- copper–constantan
- Pt–Rh
Show the answer
Answer: A. chromel–alumel General purpose.
Very high vacuum is measured by
- Bourdon tube
- McLeod gauge
- bellows
- U-tube only
Show the answer
Answer: B. McLeod gauge Compressed gas.
A rotameter is a
- variable-area meter
- head meter
- turbine meter
- magnetic meter
Show the answer
Answer: A. variable-area meter Float in taper tube.
Hot metal in furnaces is measured by a
- radiation pyrometer
- mercury thermometer
- RTD
- bimetal strip
Show the answer
Answer: A. radiation pyrometer Non-contact.
Liquid level by DP depends on
- ρgh
- flow speed
- colour
- viscosity only
Show the answer
Answer: A. ρgh Hydrostatic.
Bourdon tubes measure
- pressure
- temperature only
- flow only
- pH
Show the answer
Answer: A. pressure Elastic deformation.
The practice questions were written for this studio; they are not copied from ASTU papers. ASTU publishes no topic syllabus for these exams, so the topics are an informed guide based on diploma courses, not an official list.